So my gas furnace is cutting-out early when stage 2 heat is called for by the thermostat. Overnight, house is set to 66F. At wake-up, thermostat updates to 69F setting. Stage 2 heat fires and runs for a bit, but cuts out early before the house gets all the way to 69F. And then it tries again a couple minutes later.
I replicated this and found that a limit switch is activating (based on the status light blinks). OK... then I traced it to the temperature limit switch (using a DMM) in the heat exchanger. It is closed at start, furnace fires for a bit, then it opens and the furnace cuts out, and it then self-resets after a couple minutes, and the furnace tries again. Eventually after enough sh