I understand 50A breaker generally supports ~40A continuous (EV charging) and a 60A breaker is ~48A continuous. If the wire from the breaker to the inlet supported 50A continuous (6/3 or bigger) the next limitation would be the inlet and then cord to the generator, and then the generator itself (plug and breaker).
For sake of argument, pretend I'm trying to charge an EV at 48A, powered by a 50A inlet. Anything I should keep in mind or build for?